The MMF-300 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300(A) can be used to replace M300 modules in existing systems.
Features
MDF-300 Dual Monitor Module The MDF-300(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent twowire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panelcontrolled LED.
The CMF-300 Addressable Control Module provides FireLite intelligent control panels a circuit for Notification Appliances (horns, strobes, etc.). Addressability allows the CMF-300 to be activated through panel programming, on a select (zone or area of coverage) basis. LiteSpeed is a communication protocol developed by FireLite Engineering that greatly enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs.
Features
Addressable Mini-Monitor Module, One Style B (Class B) Initiating Device Circuit for Monitoring N/O contact devices, does not include a polling LED
The MMF-301 monitor module can be installed in a single gang junction box directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301 is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating circuit for normally open contact fire alarm and security devices. This module can be used to replace an M301 module in existing systems.
MMF-300(A) is a standard-sized module that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices.